Commissioning
5.1.6
Pre-ventilation period
Select parameter no. 785
If an output channel is set to flue gas re-circulation, attention must still be given to P 427.
5.1.7
Recirculation Delay
Select parameter no. 427
No
FMS
ETA
Short Text
Description
Min
Max
Default
785
1
1
ZEIT VO
Pre-ventilating time in seconds
0
999
30
Set the duration of pre-ventilation in this parameter.
The commissioning engineer sets this value.
P784 sets the lower limit of the pre-ventilation.
No
FMS
ETA
Short Text
Description
Min
Max
Default
427
1
1
VO Del R
Number of points of air channel of recirc. (VMS)/delay
time (FMS)
0
999
750/10
Number of points of an air channel for recirculation
(VMS) / delay time (FMS) in seconds.
With VMS it is necessary to couple the recirculation flap
delay with an air channel during pre-ventilation. There-
fore an air channel is assigned to the recirculation flap
(see P 428). The opening of this air channel now deter-
mines the moment, when the recirculation flap shall
open. Set in this parameter the number of digits the air
channel has to reach, before recirculation becomes
active.
If the device is an ETAMATIC or a FMS, set the delay
time in seconds before the recirculation flap opens,
i. e. during this period only the boiler is ventilated.
The total pre-ventilation duration (P 785) has to be
greater than the value in this parameter.
- VMS opening of the air channel for delay of the
recirculation channel (in digit)
- FMS delay time (in seconds)
0 = recirculation channel remains closed during pre-
ventilation
1... = Delay/delay time of the recirculation channel
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......