Internal Burner Firing-rate Controller
Fig. 7-2 Startup sequence
7.12
Thermostat and Control Range
The thermostat function switches the burner on and off on the basis of the temperature and/
or pressure value, but only when burner is released by the start signal. The control range is
formed by entering the controller set-point value and the parameters P 802 (switch-on point),
P803 (upper control range) and P 804 (burner OFF). The cut-off hysteresis is divided into 2
ranges. The first part lies above the set-point and forms the upper control range. The second
part lies below the setpoint and forms the lower control range.
The control range may lie asymmetrically around the setpoint.
The power control unit functions within the upper and lower control range according to its set-
tings in the parameters and the default values.
If the actual value of the control unit reaches the shut-down range, the base load request is
emitted. If the control unit’s setpoint exceed the shut-down range a control shut-off occurs.
This is done by internal processing. If the actual value drops below the lower control range, a
re-start can occur.
No
FMS
ETA
Short Text
Description
Min
Max
Default
791
0
0
Anf.Temp
Max. start-up temperature
0
999
0
Maximum start-up temperature or pressure in relation to
the actual value
Start - up circuit parameter:
Enter the actual temperature, up to which the start - up
circuit is active.
792
0
0
Anf.Leis
Start-up output
0
999
0
Burner start-up firing-rate, corresponding to the internal
firing-rate (in digit)
Set the firing-rate value at which the burner should start.
see figure start - up circuit
793
0
0
Anf.Zeit
Start-up time
0
32767
0
Burner-start-up-time in seconds
The maximum time the start - up circuit is active is set
here.
see figure start - up circuit
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......