81
9
Appendix
9.5
Aides
A13
Fault 105
During the check of the redundant curves an error was identified.
If data were provided via PC interface:
Enter curve data again for the corresponding curve set
if this is not possible:
select appropriate curve set
Clear memory
Re-enter curve
A 14
Fault 106
In checking the redundant parameters an error was identified
If data were provided via computer interface:
Read in parameter again
if this is not possible:
select the parameter
check displayed value and if necessary modify it
In order to restore the parameter, a change must be made. If the correct value is displayed,
change it for one digit and change it back again.
If several parameters are defective, repeat as necessary.
If the parameter is not included in your release level, you must request an EEPROM from
LAMTEC
A20
Fault 370
The internal communication is not functioning.
Voltage off and back on
After changing EPROM:
Check whether the monitoring program EPROM is correctly inserted
otherwise:
Change processor card.
A21
Fault 901, 904, 905,
906, 911, 912, 913,
914, 915
After changing a potentiometer, the reference must be entered again.
Voltage levels are checked in the device. These can give rise to false errors as a result of in-
correct external wiring.
Check wiring
In the case of analog inputs the reference element serves for voltage supply to the potentiom-
eters.
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......