TRIG:PROG:SOUR
Sets the condition (trigger source) for actually starting the sequence operation after
the PROGram trigger subsystem receives an INIT:PROG.
Command
TRIGger:PROGram:SOURce <character>
TRIGger:PROGram:SOURce?
Parameter
Value:
IMMediate
Execute the sequence immediately (default)
BUS
Waits for a software trigger (a *TRG, TRIG:PROG, or IEEE
488.1 get
̶
Group Execute Trigger
̶
command), and then
execute the sequence
Settings are reset to default values when an *RST command is sent.
Example
TRIG:PROG:SOUR BUS
Response: Characters