Type 67-09:
Volume calculation
This top module calculates the difference between inlet and
outlet volume, whereby an expression of the tapped volume in
open systems is obtained.
Differential volume dV=V1-V2.
Requires CCC1=CCC2 and a suitable DDD-code.
Terminal screws are not used in this module.
Type 67-0A: 2 pulse outputs for CE and CV + scheduler
See Application no. 10 on page 35, Hot water meter
The top module has the same functions as the 602-0C top
module and furthermore the module is able to simulate a cold
water temperature according to a programmed scheduler, where
the programmed temperature for T2, T3 or T4 can be
programmed with up to 12 individual dates/temperatures per
year.
See paragraph 10.1.2 concerning the function of the pulse
outputs.
Type 67-0B: RTC + 2 pulse outputs for CE and CV + prog. data
logger
Pulse output functions of this top module are identical with the
functions described under top module
602-0C.
Type 67-0B however,
is supplied with Opto FET
output
for AC/DC pulses. See
paragraph 2.2 Electrical data
as
to
specifications
of pulse outputs CE
and CV.
The top module is prepared for use in a Kamstrup radio
network together with the High Power Radio Router base
module 6020084, read data being transferred to the system
software via network unit RF Concentrator. The prog. data
logger function is configured for the specific meter where it is
installed by using the serial number. If the module is removed
and installed in another meter, the configuration is set to
default values. Logger interval: 60 minutes.
See
paragraph 10.1.2 concerning the function of the
pulse
outputs.
See
paragraph 6.13 Data loggers.
Type 602-0C: 2 pulse outputs for CE and CV
This top module has two configurable pulse outputs, which are
suitable for volume and energy pulses for heat meters, cooling
meters and combined heat/cooling meters.
The pulse resolution follows the display (fixed in the CCC-code).
E.g. CCC=119 (qp 1.5): 1 pulse/kWh and 1 pulse/0.01 m
3
.
The pulse outputs are optoinsulated and can be charged with
30 VDC and 10 mA.
Normally, energy (CE) is connected to 16-17 and volume (CV) to
18-19, but other combinations can be selected via the PC
program METERTOOL, also used to select pulse duration 32 or
100 ms.
See paragraph 10.1.2 concerning the function of the pulse
outputs.