5
Installation
5.1
Inlet pipe and outlet pipe placing
Prog. number
A
MULTICAL
®
602 is programmed for flow sensor placing in either
inlet or outlet pipe. Below diagram shows the installation
conditions for:
Heat meters
Cooling meters
Heat/cooling meters
Flow sensor placing:
k-factor
table
- Inlet pipe (at T1)
3
- Outlet pipe (at T2)
4
Formula: k-factor
Prog.:
Hot
pipe
Cold
pipe
Installation:
Heat meter
E1=V1(T1-T2)k
k-factor with
T1 in
Inlet table
A=3 (Flow
sensor in
Inlet pipe)
V1 and
T1
T2
k-factor with
T2 in
Outlet table
A=4 (Flow
sensor in
Outlet pipe)
T1
V1 and
T2
Cooling meter
E3=V1(T2-T1)k
k-factor with
T1 in
Outlet table
A=3 (Flow
sensor in
Inlet pipe)
T2
V1 and
T1
k-factor with
T2 in
Inlet table
A=4 (Flow
sensor in
Outlet pipe)
V1 and
T2
T1