6.12
Tariff functions
MULTICAL
602 has 2 extra registers TA2 and TA3 to accumulate heat energy or cooling energy (EE=20 accumulates
volume) in parallel to the main register based on a programmed tariff condition. No matter which tariff form is
selected the tariff registers are indicated as TA2 and TA3 in the display.
The main register is always accumulated as it is considered a legal billing register, irrespective of the selected tariff
function. The tariff conditions TL2 and TL3 are monitored before each integration. When the tariff conditions are
fulfilled the consumed heat energy is counted in either TA2 or TA3, in parallel to the main register.
To each tariff function two tariff conditions, TL 2 and TL3 are connected, which are always used in the same tariff
type. Therefore, it is not possible to "mix" two tariff types.
Example: EE=11 (Power tariff)
TA2 shows the consumed energy…
…over the power limit TL2 (but under TL3)
TA
3
Main re
g
is
ter
TA
2
0
10
20
30
40
50
60
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Pow
e
r (kW
)
Number of integrations
Power tariff