Structural Information
The Magnum 86072 firebox/smoke dome assembly
has a load capacity that allows for the fireplace system to carry
a limited amount of straight, vertical DM chimney sections.
The load capacity for the 86072, stated as maximum DM
chimney heights without additional structural support is as
follows:
Magnum 86072: Max. 22 feet of DM Chimney Flue
This chimney height is for straight chimneys (no
offsets) and are exclusive of brickledge.
Important:
DM chimneys taller than the above listed maximum
height require a steel angle (minimum of 4” x 4” x 3/8”) be set
across the Magnum 86072 firebox opening when assembling
the unit as a structural lintel.
This steel lintel shall span the Magnum 86072 firebox
opening, bearing fully on the front 4 inches of the firebox side
wall components. The vertical leg of the angle steel lintel should
turn up and sit in front of the Magnum 86072 damper beam
component. (Figure 102)
Important:
For DM chimneys with both offsets and a
brickledge it is important to fully support the last offset block
where the chimney returns to vertical. This is required in order
to provide complete vertical support for the brickledge and its
related loads.
Important:
When placing steel angles or any other steel support
members into the Magnum 86072 fireplace structure maintain a
2” minimum air space around steel members for clearance to
combustible members and combustible surfaces.
FIGURE 102
FIGURE 103
FIGURE 104