Combustible sheathing such as plywood and particle board may be used to cover the front face of the Magnum 86072
smoke dome and be in direct contact with it. If sheathing protrudes in front of the firebox, application of such combustible
sheathing must assure that the sheathing is held a minimum of nine inches (9”) away from each side of the Magnum 86072
opening and a minimum of twenty four inches (24”) above the top of the Magnum 86072 opening. (Figure 62 & 63)
Do not build a combustible framed wall out in front of the Magnum 86072 firebox. If combustible sheathing and framing
are to be installed across the front face of the Magnum 86072 smoke dome, then the framing and sheathing must be held a
minimum of twenty four inches (24”) above the top of the Magnum 86072 firebox opening. This means that combustible framing
and sheathing across the smoke dome front must be kept 16” above the Magnum 86072 damper beam.
Required Clearances (when sheathing protrudes beyond front of firebox)
26
FINISHED OPENING
9”
MIN
9”
MIN
24”
WOOD (FLAMMABLE)
SHEATHING
9”
MIN
9”
MIN
4” FIRE BRICK
on SIDE WALLS ONLY
4”
MIN
4”
MIN
1 1/4”
MIN
FIGURE 62
FIGURE 63