Chapter 3. Installation
35
7. If the load platform is not at its lowest position, lower the load platform to its lowest
position.
8. Move the lift tool to a position near the rear of the cabinet.
Note: If you are passing through a narrow passage or door, it might be necessary to
rotate the drawer on the load platform.
9. Set the wheel brake by pressing down on the wheel brake pedal.
10. Locate the anti-tips bars. If they are not attached, attach them to the lift tool, as
follows:
a. Pull up on the leg lock pins and insert the anti-tip bars inside the legs.
b. Pull on the legs and anti-tip bars to ensure that they are locked into position.
c. Raise the platform to allow enough room to attach the anti-tip bracket.
d. Secure the anti-tip bars by using the anti-tip bracket and bolt.
11. Adjust the load platform to the same level (height) of the cabinet guide rails.
12. Turn the winch crank counterclockwise, 1/4 turn, to set the winch brake.
13. Set the wheel brake and place the wheel chocks around the wheels.
14. Remove the retention straps. Slide the switch into the cabinet.
15. Remove the wheel chocks, release the wheel brake, and move the lift tool away
from the cabinet.
16. Fasten the two flat left and right mount brackets that are on the chassis to the
cabinet mount brackets.
17. Reinstall the cabinet doors after you put the SAN256N director in place.
Installing SAN256N into SANC40 cabinet
Use this procedure to install a SAN256N chassis into a SANC40 cabinet.
Required Kit: SAN256N director to SANC40 cabinet Upgrade: 1016969-001
Important: When the SAN256N director is shipped in conditions of extreme (high/low)
temperature and/or humidity, allow 24 hours for environmental stabilization of the
SAN256N chassis at room temperature. This 24-hour environmental stabilization period
must be accomplished in the room/area where the installation will take place. The ESD
bag/shipping materials must be removed to allow proper environmental stability prior to
the installation of the SAN256N director.
Notes
• Use a hydraulic, electrical, or mechanical lifting device that can safely handle a
minimum weight of 250 lbs. to remove the chassis from the wooden skid.
• IBM recommends that a minimum of two people be involved in the removal of the
chassis from the shipping skid and installation of the chassis into the designated
cabinet/rack.
• Due to the weight of the SAN256N, approximately 210 lbs. fully loaded, IBM
recommends that each installer wear a protective back brace while positioning the
chassis into the cabinet.
Attention: Refer to safety notices before starting an installation.
Содержание TotalStorage SAN256N Director 2045-N16
Страница 2: ......
Страница 3: ...IBM TotalStorage SAN256N Director 2045 N16 Installation and Maintenance Guide GC26 7714 00...
Страница 10: ...SAN256N Director 2045 N16 viii...
Страница 12: ...SAN256N Director 2045 N16 x...
Страница 18: ...SAN256N Director 2045 N16 xvi...
Страница 26: ...SAN256N Director 2045 N16 6...
Страница 84: ...SAN256N Director 2045 N16 64...
Страница 94: ...SAN256N Director 2045 N16 74...
Страница 97: ...Chapter 5 Hardware maintenance procedures 77 Figure 33 SAN256N director front chassis FRU locations 1 2...
Страница 120: ...SAN256N Director 2045 N16 100...
Страница 142: ...SAN256N Director 2045 N16 122...
Страница 144: ...SAN256N Director 2045 N16 124...
Страница 156: ......
Страница 157: ...Printed in USA GC26 7714 00...