SAN256N Director 2045-N16
32
Floor tile cutouts
Raised flooring with tile cutouts to accommodate forced airflow and cable access (power
cables, braided ground strap, and fiber optic cables) requirements are preferred and
recommended.
For cooling requirements of the SAN256N director, raised floor tile positioning
requirements and measurements should be followed as indicated in the figure below for
each cabinet to be installed.
Floor tile cutout for cabling should be in accordance with the measurements shown in
the figure below; a 27.94 cm by 15.24 cm (11 inch by 6 inch) cutout in the front center of
one floor tile which is for the AC power and fiber optic cables. The second floor tile must
be a checkerboard perforated pattern, allowing a 60% open airflow area..
Figure 24. Floor tile layout for the SAN256N director
Place the cabinet into position in accordance with the customer’s approved site floor
plans that were used during the planning site survey physical layout.
Locate the remaining shipping boxes that contain the fan assemblies, cables,
Customer’s Spares Kit, and other cabinet installation parts.
Enlarged view of standard 61 by 61 cm (24 by 24 inch) floor tiles
Checkerboard perforation
pattern allowing 60% open area
for airflow
Floor tile directly
6”
under SANC40 cabinet
Floor Tile directly behind
SANC40 cabinet
(15.24 cm)
11”
Placement outline of
SANC40 cabinet on floor tiles
Front of each SANC40 cabinet
(27.94 cm)
Содержание TotalStorage SAN256N Director 2045-N16
Страница 2: ......
Страница 3: ...IBM TotalStorage SAN256N Director 2045 N16 Installation and Maintenance Guide GC26 7714 00...
Страница 10: ...SAN256N Director 2045 N16 viii...
Страница 12: ...SAN256N Director 2045 N16 x...
Страница 18: ...SAN256N Director 2045 N16 xvi...
Страница 26: ...SAN256N Director 2045 N16 6...
Страница 84: ...SAN256N Director 2045 N16 64...
Страница 94: ...SAN256N Director 2045 N16 74...
Страница 97: ...Chapter 5 Hardware maintenance procedures 77 Figure 33 SAN256N director front chassis FRU locations 1 2...
Страница 120: ...SAN256N Director 2045 N16 100...
Страница 142: ...SAN256N Director 2045 N16 122...
Страница 144: ...SAN256N Director 2045 N16 124...
Страница 156: ......
Страница 157: ...Printed in USA GC26 7714 00...