Item
Description
Defa
ult
Valu
e
Value Range
Bat
mod
e
shut
delay
When the delay time reaches
the value after UPS transfers to
battery mode, the UPS powers
off. If this parameter is set to
0S, the shutdown delay
function is disabled. If the delay
time is set to other values,
ensure that backup time is
greater than shutdown delay
time of battery mode.
Otherwise, the power supply to
loads may be disconnected. The
parameter is configurable in
non-battery mode or non-
battery ECO mode.
NOTE
● If the mains input and bypass
input use the same power
source, the system powers off
when the shutdown delay in
battery mode reaches the
preset value. If the mains input
and bypass input use different
power sources, the system
transfers to bypass mode when
the shutdown delay in battery
mode reaches the preset value.
● The Bat mode shut delay
parameter is not synchronized
in a parallel system. In a
parallel system, set this
parameter to the same value
for different UPSs.
0s
0–600s
The value interval is 30s.
For example, the value
can be 0s, 30s, 60s, and
90s.