Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0060-07 Inverter
fault
Critical
Automa
tic
The UPS starts automatically
after shutdown.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
● The ambient
temperature exceeds
40ºC.
● The air channel is
blocked.
● The air filter is
blocked by dust.
● The fan is abnormal.
Measures:
● Decrease the
ambient
temperature.
● Keep the air intake
and exhaust vents of
the UPS
unobstructed.
● Clean or replace the
air filter.
● Clean off the foreign
objects around the
fan. If the alarm
persists, contact
Huawei technical
support for repair.
0060-08 Inverter
fault
Critical
Manual
/Power-
off
The UPS shuts down.
Possible cause: The DSP
or CPLD chip is faulty.
Measure: Contact
Huawei technical
support for repair.