Model
Wiring
Terminal
Number
of
Phases
Rated
Voltage
Externa
l Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
Torque
for
Tighteni
ng Bolts
dual-live-
wire
output)
Battery
-
± 240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Dual-live-
wire
Output
2
208 V
AC/220 V
AC
100 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(single-
phase
input
single-
phase
output)
Input
1
220 V
AC/230 V
AC/240 V
AC
100 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
Battery
-
± 240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output
1
220 V
AC/230 V
AC/240 V
AC
100 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(three-
phase
input
single-
phase
output)
Bypass
input
1
220 V
AC/230 V
AC/240 V
AC
100 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
Mains input 3
380 V
AC/400 V
AC/415 V
AC
50 A
(feature
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N m
Battery
-
± 240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output
1
220 V
AC/230 V
AC/240 V
AC
100 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(three-
phase
input
three-
Bypass
input
3
380 V
AC/400 V
AC/415 V
AC
50 A
(feature
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N m
Mains input 3
UPS2000-G- (6 kVA-20 kVA)
User Manual
3 Installation
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
32