Table 9-9 Backup time parameters for the ESS-240V12-7AhBPVBA01 battery pack
(6 kVA, battery efficiency assumed as 94%)
Load (%)
Load (W)
One
Battery
pack
(min)
Two
Battery
packs
(min)
Three
Battery
packs
(min)
Four
Battery
packs
(min)
100%
5400
6
19
29
46
80%
4320
9
25
43
57
50%
2700
19
46
68
92
30%
1620
36
77
120
174
Figure 9-1 Backup time parameters for the ESS-240V12-7AhBPVBA01 battery pack
(6 kVA, battery efficiency assumed as 94%)
UPS2000-G- (6 kVA-20 kVA)
User Manual
9 Technical Specifications
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
120