Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0134-01 Ambien
t
overhu
midity
Minor
Possible causes:
● The ambient
humidity in the UPS
equipment room
exceeds the alarm
threshold (default
value: 90%).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
0135-01 Ambien
t
underh
umidity
Minor
Possible causes:
● The ambient
humidity in the UPS
equipment room is
below the alarm
threshold (default
value: 10%).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
170