Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0159-01 On
battery
Minor
Automa
tic
The UPS may power off if
batteries are abnormal.
Possible causes:
● The mains input is
abnormal.
● The UPS is in battery
self-check state.
● The mains loading
capability is
insufficient.
Measures:
● Check the mains
input. If the mains
input is abnormal,
wait until the mains
input recovers.
● Check whether the
UPS is in battery
self-check state.
● Reduce the load or
replace the UPS with
a larger-capacity
UPS.
0340-01 Maint.
breaker
ON
Minor
Automa
tic
The UPS transfers to bypass
mode.
Possible cause: The
maintenance circuit
breaker is ON during
UPS maintenance.
Measure: Switch off the
maintenance circuit
breaker after
maintenance.
61440-0
1
Flash
fault
Critical
Automa
tic
Files may be damaged.
Possible cause: The
flash memory cannot be
properly read or written.
Measure: Contact
Huawei technical
support for repair.