Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0023-01 Batt.
overtem
p.
Minor
Automa
tic
An alarm is generated, and
the battery lifespan is
affected.
Possible causes:
● The ambient
temperature of
batteries exceeds the
battery high
temperature alarm
threshold (default
value: 50°C).
● The battery charge/
discharge current
exceeds the upper
threshold.
Measures:
● Install more cooling
equipment such as
air conditioners.
● Control the battery
charge/discharge
current by reducing
loads.
0025-01 Batt.
overvolt
.
Minor
Automa
tic
An alarm is generated, and
the battery lifespan is
affected.
Possible causes:
● The configured
number of batteries
is less than the
actual number.
● The battery string
charge voltage
exceeds the upper
threshold.
Measures:
● Check battery
parameter settings.
● Disconnected the
external battery
charger, check
whether the alarm is
cleared. If not,
contact Huawei
technical support for
repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
147