Table 4-21 ECO settings
Item
Description
Defa
ult
Valu
e
Value Range
Max.
voltage
Upper threshold for the ECO voltage.
In ECO mode, when the difference
between the bypass voltage and the
rated voltage is greater than this
value, the system determines that the
ECO voltage is abnormal and
transfers to normal mode. This
parameter is configurable only
after the inverter is shut down.
10%
5%, 6%, 7%,
8%, 9%, 10%
Min.
voltage
Lower threshold for the ECO voltage.
In ECO mode, when the difference
between the bypass voltage and the
rated voltage is lower than this value,
the system determines that the ECO
voltage is abnormal and transfers to
normal mode. This parameter is
configurable only after the inverter
is shut down.
10%
5%, 6%, 7%,
8%, 9%, 10%
Frequenc
y range
ECO frequency range. In ECO mode,
when the difference between the
bypass frequency and the rated
frequency is beyond this range, the
system determines that the ECO
frequency is abnormal and transfers
to normal mode.
The Frequency range parameter is
associated with the bypass frequency
range and must be less than the
current bypass frequency range. This
parameter is configurable only
after the inverter is shut down.
±2
Hz
±0.5 Hz, ±1 Hz,
±2 Hz,±3 Hz
Single
UPS ECO
Determine whether to support ECO
mode on a single UPS (ECO mode is
not supported in a parallel system).
Disa
bled
Disabled,
Enabled
●
Power Segment screen
Figure 4-32 Power Segment screen
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
65