Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0032-01 Batt.
OVP
Critical
Automa
tic
An alarm is generated, and
the battery lifespan is
affected.
Possible causes:
● The configured
number of batteries
is less than the
actual number.
● The actual number
of batteries does not
meet specifications.
● The charger is
abnormal.
Measures:
● Check that the
configured number
of batteries matches
the actual number.
● Check that the actual
number of batteries
meets requirements.
● Disconnected the
external battery
charger, check
whether the alarm is
cleared. If not,
contact Huawei
technical support for
repair.
0034-01 Remaini
ng cap.
warning
Minor
Automa
tic
If no action is taken,
continued discharge will
result in system shutdown
due to EOD.
Possible cause:
● The battery
discharge lasts too
long.
● The mains input is
abnormal.
● The number of
batteries or battery
capacity is incorrectly
set.
Measure:
● Check the mains, and
charge batteries in a
timely manner.
● Check the configured
battery capacity.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
152