Output screen
Figure 4-29 Output screen
NO TE
The UPS supports 208 V output. In the case of 208 V output, the power is derated to
90%. The cable connections and cable connections for 208 V and 200 V are similar.
Table 4-19 Output settings
Item
Description
Default Value Value Range
Output
mode
Set the system output
mode. The input mode is
identified automatically
by the system. This
parameter is
configurable only after
the inverter is shut
down.
This
parameter is
not
configurable
for the 6
kVA/10 kVA
models. The
default value
is Single-
phase.
15 kVA/20
kVA: Three-
phase
Single phase,
Three-phase
Voltage
level
Indicates the system
output voltage level.
After you change the
voltage level, the upper
threshold for bypass
voltage is restored to the
default value (15% or
20%). This parameter is
configurable only after
the inverter is shut
down.
6 kVA/10 kVA:
220 V
15 kVA/20
kVA single-
phase output:
220 V
15 kVA/20
kVA three-
phase output:
380 V
6 kVA/10 kVA:
208 V, 220 V, 230
V, 240 V
15 kVA/20 kVA
single-phase
output: 208 V, 220
V, 230 V, 240 V
15 kVA/20 kVA
three-phase
output: 380 V, 400
V, 415 V
UPS2000-G- (6 kVA-20 kVA)
User Manual