NO TE
Perform the following operations in a parallel system using the TN-C power distribution
system:
● Short-circuit the input N and PE, and short-circuit the battery port N.
● It is recommended that you connect AC loads and battery packs only to the UPS PE
terminal.
● The recommended type for magnetic rings 1, 2, and 3 is DN85Hx4 or E2Fx4.
Table 2-3 Specifications of magnetic rings from three vendors
Vendor
Magnetic Ring
DMEGC
R10K
TDK
HS10
TDG
TS10
NO TE
The magnetic conductivity of manganese and zinc magnetic rings is greater than 10,000,
and the recommended internal diameter of magnetic rings is greater than 10 mm (easy for
wire coiling). The number of coiling circles is 5 or greater.