Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0030-01 UPS
inter
overtem
p.
Minor
Automa
tic
The power supply from the
UPS and system is not
affected.
Possible causes:
● The ambient
temperature exceeds
40°C.
● The air channel is
blocked.
● The air filter is
blocked by dust.
● The fan is abnormal.
Measures:
● Decrease the
ambient
temperature.
● Keep the air intake
and exhaust vents of
the UPS
unobstructed.
● Clean or replace the
air filter.
● Clean off the foreign
objects around the
fan. If the alarm
persists, contact
Huawei technical
support for repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
151