Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0064-02 OL
timeout
Critical
Manual
/Power-
off
The UPS cannot be started.
Possible cause: The load
exceeds the rated
bypass loading capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
0065-01 Power
segmen
t
Minor
Manual
/Power-
off
Secondary loads are
disconnected.
Possible cause: The load
exceeds the rated
loading capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
0065-02 Power
segmen
t
Minor
Automa
tic/
Manual
Possible causes:
● The battery voltage
is below the battery
protection voltage.
● The battery
discharge time
exceeds the battery
protection time.
Measures:
● Check the battery
voltage.
● Modify the power
segment settings on
the LCD.
0066-01 Output
overloa
d
Minor
Automa
tic
Continuous overload causes
the UPS to transfer to bypass
mode or supply no power.
Possible cause: The load
exceeds the rated
loading capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
0066-02 Output
overloa
d
Minor
Automa
tic
Continuous overload causes
the UPS to supply no power.
Possible cause: The load
exceeds the rated
bypass loading capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.