Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0096-01 Abnorm
al ECO
volt.
Minor
Automa
tic
Transfer to bypass mode is
prohibited. If the bypass is
supplying power, the UPS
transfers to another working
mode.
Possible cause: The ECO
input is abnormal.
Measure: Check
whether the ECO input
voltage or frequency
exceeds the configured
range. If yes, change the
range or wait until the
bypass input recovers.
0105-05 Comm.
failed.
Minor
Automa
tic
The monitoring module
cannot monitor the digital
signal processor (DSP) of the
power module.
Possible causes:
● The communications
cable is faulty.
● An internal fault
occurs in the UPS.
Measures:
● Check the
communications
cable.
● Contact Huawei
technical support for
repair.
0125-01 Incon.
paral.
param.
Critical
Automa
tic
An alarm is generated, and
all the UPSs in the parallel
system cannot start
inverters.
Possible cause: The
parallel parameters are
not set consistently on
the UPSs.
Measure: Set the
parallel parameters
consistently, or perform
parallel parameter
synchronization.
NOTE
After you perform parallel
parameter
synchronization, contact
Huawei technical support
if some parallel
parameters are still
inconsistent.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)