Table 9-11 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery
pack (15 kVA, battery efficiency assumed as 94%)
Load (%)
Load (W)
Two
Battery
Packs
(min)
Four
Battery
Packs
(min)
Six Battery
Packs
(min)
Eight
Battery
Packs
(min)
100%
13500
7
19
32
48
80%
10800
9
26
44
57
50%
6750
18
48
70
96
30%
4050
35
79
125
171
Figure 9-3 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery pack
(15 kVA, battery efficiency assumed as 94%)
UPS2000-G- (6 kVA-20 kVA)
User Manual
9 Technical Specifications
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
122