9.7 ECO Specifications
Table 9-13 ECO specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA
ECO voltage
tolerance
Default value: ±10% (configurable on the LCD)
The range is ±5% to 10%
ECO frequency
tolerance
Default value: ±2 Hz (configurable on the LCD)
The range is ±0.5 Hz to ±3 Hz
9.8 Parallel System Specifications
Table 9-14 Parallel system specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA
Number of UPSs
in parallel (two
live wires)
1+1
Number of UPSs
in parallel (other
mode except two
live wires)
≤ 4
NO TE
The UPS2000-G-15 kVA/20 kVA (single-phase input single-phase output) supports 3+1
parallel systems at most, instead of 4+0 parallel systems.
9.9 Safety Regulations and EMC
Table 9-15 Safety regulations and EMC
Item
Standards Compliance
Remarks
Electromag
netic
compatibili
ty
Conducted radiation: IEC/EN
62040-2
-
Voltage change, fluctuations,
and flicker I ≤ 16 A, IEC/EN
61000-3-3; 16 A < I ≤ 75 A,
IEC/EN 61000-3-11
-
UPS2000-G- (6 kVA-20 kVA)
User Manual