Table 4-26 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Default Value
Value Range
Number
of
batteries/
Positive
batteries
and
Negative
batteries
Set the number of batteries.
When the number of
batteries N is less than 20,
the system output power is
derated to N/20 in battery
mode. The parameter is
configurable in non-battery
mode or non-battery ECO
mode. You need to set
Number of batteries on the
UPS2000-G-6 kVA/10 kVA,
and set two battery strings
(positive and negative) on
the UPS2000-G-15 kVA/20
kVA.
0
16–20
Battery
capacity
Set the battery string
capacity. (Battery capacity is
the sum of each battery
string. Set the battery
capacity based on the
actual value.) The
parameter is configurable in
non-battery mode or non-
battery ECO mode.
6 kVA standard
model: 7 Ah
6 kVA long
backup time
model: 40 Ah
10 kVA
standard
model: 9 Ah
10 kVA long
backup time
model: 65 Ah
15 kVA/20 kVA
long backup
time model: 65
Ah
7–1000 Ah
Intelli.
Hibernati
on
When it is set to enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
configurable in any mode.
Disabled
Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
configurable in any mode.
50°C
45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
configurable in any mode.
–5°C
–30°C to +5°C
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
72