Sets and checks teamwork control information based on the requirements of
the smart cooling product.
●
Running
Checks the component status, system parameters, and the name, control and
operating status, and other related information of the components in the
current smart cooling product system.
●
Alarms
Checks the active and historical alarms of the smart cooling product, and
deletes the historical alarms.
●
Settings
Sets the involved parameters for the operation of the smart cooling product.
●
Maint
Checks or deletes the logs or component total runtime/run factor, manually
diagnoses each component, calibrates the sensor and touch screen, exports
data, and upgrades the system.
●
About
Checks the model, manufacturer, monitoring version, detail version
information, and electronic label of the ACC.
4.4 Initial Configuration
4.4.1 Setting Temperature and Humidity Values and
(Optional) Enabling T/H Sensors
Prerequisites
●
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
.
●
If you need to enable a humidity and temperature sensor, log in as the admin
user.
●
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
is displayed.
Figure 4-4 Setting temperature and humidity values
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)