Alar
m ID
Alarm
Name
Alarm
Severi
ty
Possible Cause
Solution
A080
CW valve
exceed
runtime
alarm
WARNI
NG
The accumulated
runtime of the
chilled water valve
exceeds the alarm
threshold.
Maintain or replace the
chilled water valve and
clear the accumulated
runtime.
A090
Cond pump
1 exceed
runtime
alarm
WARNI
NG
Condensate pump
runtime exceeds the
limit.
Maintain or replace the
condensate pump, and
clear the total runtime.
A091
Cold aisle
low
temperature
alarm
WARNI
NG
1. The temperature
sensors or
temperature and
humidity sensors are
located in
inappropriate
positions.
2. The thermal load
power is low.
3. The ambient
temperature is
below the lower
threshold.
4. The low
temperature alarm
threshold is
inappropriate.
5. The value
detected by the
temperature sensor
or temperature and
humidity sensor is
different from the
actual value.
6. The air filters are
blocked.
7. The chilled water
valve is stuck or
faulty.
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Contact Huawei
technical support.
3. Measure the ambient
temperature. Check
whether other causes
exist if the alarm
persists in a long time
after startup.
4. Adjust the low
temperature alarm
threshold.
5. Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
6. Maintain or replace
the air filters.
7. Maintain or replace
the chilled water valve.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
6 System Operation and Maintenance
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
136