Alar
m ID
Alarm
Name
Alarm
Severi
ty
Possible Cause
Solution
A093
High
humidity
alarm
WARNI
NG
1. The thermal load
power is low.
2. The ambient
humidity exceeds
the upper threshold.
3. The temperature
and humidity sensor
is not installed in a
proper position.
4. The high humidity
alarm threshold is
inappropriate.
5. The value
detected by the
temperature and
humidity sensor is
different from the
actual value.
1. Contact Huawei
technical support.
2. Measure the ambient
humidity.
3. Adjust the position of
the temperature and
humidity sensor.
4. Adjust the high
humidity alarm
threshold.
5. Calibrate or replace
the temperature and
humidity sensors.
A094
Low
humidity
alarm
WARNI
NG
1. The ambient
humidity is below
the lower threshold.
2. The temperature
and humidity sensor
is not installed in a
proper position.
3. The low humidity
alarm threshold is
inappropriate.
4. The value
detected by the
temperature and
humidity sensor is
different from the
actual value.
1. Measure the ambient
humidity.
2. Adjust the position of
the temperature and
humidity sensor.
3. Adjust the low
humidity alarm
threshold.
4. Calibrate or replace
the temperature and
humidity sensors.