Parameter
Description
Configuration
Principle
Default
Value
group rotate at
the same speed.
Cascade
function
After the requirement
control is enabled,
you can configure
Cascade function.
The cascade function
starts standby smart
cooling products if
the active one cannot
meet the
refrigerating
requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Differential
pressure
sharing
When this parameter
is enabled, the smart
cooling product,
which is not
configured with the
differential pressure
sensor in the group,
is logically controlled
by using the acquired
value of the
configured
differential pressure
sensor.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with differential
pressure sensors.
Disable
Cold aisle
temperature
and
humidity
sharing
When this parameter
is enabled, the smart
cooling product,
which is not
configured with the
cold aisle T/H sensor
in the group, is
logically controlled by
using the acquired
value of the
configured cold aisle
T/H sensor.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with cold aisle T/H
sensors.
Disable
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)