Name
Specifications
Quanti
ty
Remarks
OT
terminal
Naked Crimping Terminal, OT, 6
mm
2
, M6, Tin Plating, Insulated
Ring Terminal, 12-10 AWG, yellow
6 PCS
Standard
configuration;
delivered with the
product
Cord end
terminal
Common Terminal, Conductor
Cross Section 6 mm
2
, Length 20
mm, Insertion Depth 12 mm, Black
12 PCS
Standard
configuration;
delivered with the
product
Cable tie
G200IUV (3.6 x 200), Anti-
Ultraviolet And Anti-Freeze, Black
15 PCS
Standard
configuration;
delivered with the
product
Table 3-5 Cables and switches required (NetCol5000-C030/C032)
Name
Specifications
Quanti
ty
Remarks
Power
cable
Electronic|Electric Cable, 300 V/500
V, 60227 IEC10(BVV), 3 x 2.5 mm
2
,
27 A, Outdoor Cable, CCC/CE
2 PCS
Optional; same
cable parameters
for the active and
standby routes
Teamwork
networkin
g and
monitoring
cable
Signal cable, shielded straight-
through cable, 10 m, MP8-II,
CC4P0.5GY (S), MP8-II, FTP
1 PCS
Optional
Fuse
Slow Blow Fuse, 500 V, 3.15 A
2 PCS
Standard
configuration;
delivered with the
product
OT
terminal
Naked Crimping Terminal, OT, 2.5
mm
2
, M6, Tin Plating, Insulated
Ring Terminal, 16-14 AWG, Blue
6 PCS
Standard
configuration;
delivered with the
product
Cord end
terminal
Common Terminal, Conductor Cross
Section 2.5 mm
2
, Length 20 mm,
Insertion Depth 12 mm, Blue
12 PCS Standard
configuration;
delivered with the
product
Cable tie
G200IUV (3.6 x 200), Anti-
Ultraviolet And Anti-Freeze, Black
15 PCS Standard
configuration;
delivered with the
product
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
36