Parameter
Setting Method
Link
Enable the connection between the device and the WiFi
network.
IP, Port, and
devAddr
Enter the values as planned. For details, see values on the
Modbus settings screen.
Step 6 Tap Login after the parameters are set.
Step 7 After login, tap Power-on password activation on the screen. The screen shown
in
is displayed, indicating whether to start the smart cooling product.
Figure 4-23 Online boot
Step 8 Tap OK and follow instructions as prompted on the screen until the success
message for the startup is displayed on the screen.
----End
4.6 Startup Wizard
Context
The startup wizard allows for commissioning of components such as the fan,
humidifier and chilled water valve. It also supports component automatic
operation and automatic device checking.
After you power on the smart cooling product for the first time, the screen
displays the Wizard Startup. You can select to commission the smart cooling
product or not. If you select to commission it at other times, choose Maint >
Wizard Startup to start commissioning.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
111