Parameter
Description
Configuration Principle
Air-side difference
pressure sensor type
Sets the measuring
range for the air side
differential pressure
sensor.
There is no default value.
Set it to 0–50 Pa.
Min indoor fan speed
Sets the minimum speed
for the indoor fan.
You are advised not to
change the value.
Max indoor fan speed
Sets the maximum speed
for the indoor fan.
You are advised not to
change the value.
----End
4.4.3 (Optional) Setting Teamwork Control Parameters
Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork
controlled smart cooling products as follows:
●
Teamwork group no.: Group the smart cooling products in same aisle or
adjacent areas as one, that is, assign one teamwork group number for them.
At most four teamwork groups can be assigned (1–4).
●
Teamwork unit address: The address for the smart cooling product in the
same group cannot be the same (address range: 1–32). The smart cooling
product with minimum address is the master one and can not be changed,
that collects, processes, and delivers data.
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings, to enter Teamwork
Settings page, as shown in
.
Figure 4-6 Teamwork settings
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)