Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
describes how to set the parameters.
Table 4-6 Teamwork settings
Parameter
Description
Configuration
Principle
Default
Value
Teamwork
group No.
The number of the
teamwork controlled
group, which is the
same for all the
devices in the group.
Set the assigned
teamwork control
number.
1
Air
conditioner
address
Smart cooling
product addresses
should be different
from each other.
Set the assigned unit
address.
NA
Enable
teamwork
CAN resistor
Indicates the build-
out resistor status of
each smart cooling
product in a
teamwork group. Set
the parameter if CAN
network is used.
● Set this parameter to
No for non-
teamwork scenarios.
● For teamwork
scenarios, set this
parameter to Yes for
the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
No
Teamwork
function
Disable or enable the
teamwork function. If
the teamwork
function is disabled,
this device is
operating according
to its own control. If
the teamwork
function is enabled,
this device works in
harmony with others
that in the same
group.
Set this parameter
based on the onsite
device heat distribution.
Disable
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
92