Alar
m ID
Alarm
Name
Alarm
Severi
ty
Possible Cause
Solution
A105
Indoor fan
failure alarm
CRITC
AL
1. The indoor fan is
faulty.
2. The cable to the
Indoor fan is not
connected properly.
3. The power supply
to the Indoor fan is
abnormal.
1. Maintain or replace
the Indoor fan.
2. Check the cable
connection to the
Indoor fan.
3. Check the power
supply to the Indoor
fan.
A118
Primary
power
failure alarm
MAJO
R
The power supply is
faulty.
Check the power supply.
A130
Humid
water inlet
solenoid
valve fault
MAJO
R
1. The cables to the
water inlet solenoid
valve are loose or
damaged.
2. The water inlet
solenoid valve is
faulty.
1. Check the cables to
the water inlet solenoid
valve.
2. Replace the water
inlet solenoid valve.
A193
Air-side diff
pressure
sensor fault
MAJO
R
1. The differential
pressure sensor
cable is loose or
damaged.
2. The pressure tube
of the differential
pressure sensor is
reversely connected.
3. The differential
pressure sensor is
faulty.
1. Check the cable
connection to the
differential pressure
sensor.
2. Check the tube
connection to the
differential pressure
sensor.
3. Maintain or replace
the differential pressure
sensor.
A220
Wizard
startup is in
progress
WARNI
NG
Wizard startup is in
progress.
Wait until wizard
startup is complete or
clear the Wizard startup
in progress alarm
manually to exit wizard
startup.
A233
Air-side low
pressure
difference
alarm
WARNI
NG
1. Contained aisles
are poorly-sealed.
2. The differential
pressure sensor is
faulty.
1. Check that the cold
and hot aisles are well-
sealed.
2. Maintain or replace
the differential pressure
sensor.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
6 System Operation and Maintenance
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
140