Figure 7-14 Performance Maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End
7.1.11 Calibrating a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End