Menu
Parameter
Description
Configuration Principle
Teamwor
k
Settings
Teamwork group
No.
Set the assigned
teamwork
control number.
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
Air conditioner
address
Set the assigned
unit address.
Air conditioner addresses
should be different from
each other.
Teamwork function Disable or
enable the
teamwork
function. If the
teamwork
function is
disabled, this
device is
operating
according to its
own control. If
the teamwork
function is
enabled, this
device works in
harmony with
others that in
the same group.
Set this parameter based
on the onsite device heat
distribution.
Networking mode
Networking
mode for the
teamwork. The
networking
mode set on the
screen must be
consistent with
the actual
networking
mode.
Otherwise, the
teamwork
control function
will be
unavailable.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control
over a CAN bus, MAC_CAN
network teamwork control
over an FE port.
System
Optional
Parts
Cold aisle sensor 1–
5
Cold aisle
sensors can be
set to Enable or
Disable.
If a T/H sensor outside the
cabinet is deployed in the
cold aisle, enable the T/H
sensor.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
81