FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
7 System Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
55
Figure 7-13
Heat detector installation reference line
Step 11
Press
RESET
to reset the fire alarm control panel.
Step 12
(Optional) Check whether the fire alarm signals are reported to the management system.
Step 13
Reconnect cables to the electromagnetic valve.
Figure 7-14
Connecting cables to the electromagnetic valve
Step 14
Remove the safety pin after verifying that the fire extinguishing system is working properly.