7 System Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
58
7.5 Fire Extinguishing System Commissioning (CE)
Prerequisites
The extinguishant control panel has been powered on.
The management system is working properly.
Before commissioning the fire extinguishing system, remove the electrical actuator from
the container valve of the fire cylinder. This prevents the extinguishant release due to
misoperations, and prevents accidental damage during the commissioning. After the
commissioning of the fire extinguishing system, reinstall the container valve to the
electrical actuator.
To avoid damage to the heat detector, keep a proper distance between the heating device
and the heat detector during the commissioning.
Preparations
Tools: multimeter, smoke pistol, heating device, flat-head screwdriver, Phillips screwdriver,
step ladder
Documents: fire extinguishing system conceptual diagram (CE), fire extinguishing device
layout diagram (CE)
Skill requirement: fire engineer
For the diagrams, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
Remove the electrical actuator from the fire cylinder.
If the electrical actuator is installed on the fire cylinder, remove the electrical actuator from the container
valve of the fire cylinder.
Step 2
Connect the terminals on the electrical actuator to the extinguishant control panel.
If the electrical actuator is not installed on the fire cylinder, connect the terminals on the electrical
actuator to the extinguishant control panel.
Verify that the electrical actuator ejector is reset. If the ejector is not reset, press the ejector.
Step 3
Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables to the extinguishant control panel.
Step 4
Flip the key leftward to
Auto & Manual
, and set the extinguishant control panel to
Auto &
Manual
.