FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
9 Commissioning Core Components
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
99
2.
Press
S12
again to display month and date in the format of
? ? ? ?
. Press
S11
to adjust
the month, which changes cyclically between 1 and 12. Then press
S10
to adjust the date,
which changes cyclically between 1 and 31.
3.
Press
S12
again to display hour and minute in the format of
? ?:? ?
. Press
S11
to adjust
the hour, which ranges from 0 to 23. Then press
S10
to adjust the minute, which ranges
from 0 to 59.
4.
Press
S12
again to finish the time setting. The indicator H11 goes off. The nixie tube
displays the hour and minute.
Step 5
Start or stop the fire alarm sounder.
When the keypad is unlocked, press
ALARM BELL
to start or stop the fire alarm sounder.
After the fire alarm sounder is started, the indicator beside the button turns on.
Step 6
Start or stop the fire alarm horn/strobe.
When the keypad is unlocked, press
HORN/STROBE
to start or stop the fire alarm
horn/strobe. After the alarm is started, the indicator beside the button turns on.
----End
9.4.2 Commissioning the Emergency Lights (standard)
Prerequisites
The sockets of the emergency light have been powered on.
Preparations
Tools: step ladder, needle-shaped tool
Documents required: power supply and distribution system diagrams, fire extinguishing
device layout diagram (standard)
Skill requirement: fire engineer
For the diagrams, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
When you press down the
TEST
button on the emergency light, the emergency light turns on.
When you release the
TEST
button, the emergency light turns off.
Step 2
When you unplug the power plug of the emergency light, the emergency light turns on. When
you stab the small hole shown in the figure with a needle-shaped tool, the emergency light
turns off.
You can also turn off the emergency light by pressing and holding the
TEST
button for more than
5s.
If the result expected for each step appears, the emergency light is working properly.