FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
4 Preparations for Power-On Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
4.5 Preparing for the Cooling System Power-On
Commissioning
4.5.1 Preparation Process
Figure 4-1
Preparing for the cooling system power-on commissioning
4.5.2 Material preparations for the secondary refrigerant
Secondary Refrigerant Selection Rules
The secondary refrigerant can be either water or glycol solution. Rules for selecting the
secondary refrigerant are as follows:
If the local lowest temperature recorded is above 0°C and municipal water quality meets
requirements, it is recommended that municipal water be used as the secondary
refrigerant.