Operation
SDC / DHC
44
EN2H-0221GE51 R0812
5.1.2.8 "Manual mode" / "Emission measurement" button
5.1.2.8.1 Manual mode
If this button is pressed and held longer than 5 s in the basic
display, the controller is switched to manual mode. In this
operating mode, the required heat generator temperature is
specified manually with the input button
according to the
respective heating need.
A controller set to manual mode has no effect in heat circuit
expansion.
The heat generator setpoint is set between the minimum and
maximum heat generator temperatures and appears flashing at
the bottom left-hand side. The current heat generator temperature
appears statically on the right-hand side in the basic display. The
set switching differential corresponds to the value of automatic
control and is symmetrical to the set value.
Controller malfunctions (emergency operation), errors
The maximum heat generator temperature limit is paramount to
the heat generator switching differential and stops the heat
generator in case of exceedance.
With control devices operated purely as a heating circuit
expansion, the setting of the temperature has no effect.
The last value to which the control device adjusted the heat
generator temperature appears as a recommendation.
Press
button or
button, to return to the last selected
operating mode.
Application
NOTE
Cancellation
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......