Operation
SDC / DHC
98
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
24
Room control T
n
(SDW 30 only)
5 ... 240 min
35
25
Holiday operating
mode
STBY
Standby
STBY
RED
Lowering operation
26
Room setpoint
ramp
OFF, 0.5 ... 60 K/h
OFF
28
Cooling
temperature of
mixed heating
circuit
OFF, 5 to 24
OFF
39
Spread of hot-
water circuit pre-
regulator
2 ... 20 K
5
40
Offset valve
position of hot-
water circuit pre-
regulator
0 ... 100 %
0
41
Switch-on op-
timisation
OFF
OFF
1
Adaptation off
2
Adaptation on
3
Adaptation restart
42
Minimum pre-heat
time
0 ... setting value of parameter 43 0.5
43
Maximum pre-heat
time
Setting value of parameter 42 to
30 h
5
44
Min. jump back
temperature
0 ... 30 °C
5
45
Without room
sensor
0 ... 10 °C
1
46
Pre-heat time at
0 °C
0 ... 30 h
1
47
Lowering ramp
0 ... 500 %
100