Operation
SDC / DHC
82
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
03
Mixed heating
circuit 1 output
OFF
No function
3
2
Direct heating circuit
controlled by weather
conditions
3
Mixed heating circuit
controlled by weather
conditions
6
Constant regulator
7
Fixed-value regulator
8
Return maintenance
30
Mixed heating circuit as
continuous hot-water
pre-regulator (district
heating)
39
Hot-water pre-regulator
(district heating)
04
Mixed heating
circuit 2 output
For setting values, see parameter
03
3
05
Direct heating
circuit pump output
OFF
No function
2
2
Direct heating circuit
pump
4
Circulating pump
5
Electric heating element
6
Constant regulation
10
Feeder pump
11
Boiler circuit pump 1
12
Boiler circuit pump 2
13
Group alarm
14
Time switch
15
Solar charging pump
25
Cooling switchover
27
Hydraulic buffer relief
47
Electrical water heater