ATTENTION
A reset should only be carried out if all individually entered
values are to be replaced by the values specified at the
factory.
► When the PARAM. RESET
dis pla y fla s he s , pre s s the input
button
.
SET flashes in the display.
► Press and hold the input button
for 5 s.
If a reset is carried out, the RESET OK confirmation appears
briefly.
Verification is then started with a call-up of the first
parameter in the respective menu once again
.
After the parameter values are reset, a return to the first
parameter in the "System Parameter" menu occurs.
5.2.3.5 Complete reset
To reset all settings, a complete reset of the device can be carried
out.
A complete reset is initiated when the
,
,
and
keys
are pressed simultaneously until the controller restarts.
5.2.4 "DHW" menu
This menu contains all parameters required to program the hot-
water circuit, except the hot-water switching time programs.
Setting