5.2.3.3.2 Individualised night-time room temperature for each heating
circuit
► Press
button.
► Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
.
► Confirm selected circuit by pressing the input button
.
► Set flashing room temperature specification to the desired
value by turning the input button
.
► Confirm set value by pressing the
button.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
5 ... 30 °C
16 °C
5.2.3.3.3 Individualised operating mode for each heating circuit
Each heating circuit can be assigned an individualised operating
mode.
► Press
button.
► Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
.
► Confirm selected circuit by pressing the input button
.
► Select flashing operating mode by turning the input button
.
► Confirm set operating mode by pressing the
button or the
input button
.
► With short-term operating modes (ABSENT, PARTY), set
desired target value by turning the input button
and confirm
set value by pressing the input button
.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
This parameter specifies the end of heating operation depending
on the outside temperature based on the following criteria:
Setting
Setting range
Factory setting
Setting
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......