SDC / DHC
Hydraulic Components
EN2H-0221GE51 R0812
173
Parameter settings for the switch-on optimisation in the HC,
MC-1 and MC-2 menu
Para
meter
Designation
Setting range/Setting values
Factory
setting
3
Room connection (in
conjunction with room
sensor)
OFF
Display of heat generator
temperature, room sensor off,
operation active
OFF
1
Display of room temperature, room
sensor active, operation active
2
Display of room temperature, room
sensor active, operation disabled
3
Display of room temperature, room
sensor off, operation active
4
Room factor
OFF
OFF
10 ...
500%
Influence active
RC
Room controller active
26
Room setpoint ramp
OFF, 0.5 ... 60 K/h
OFF
41
Switch-on
optimisation
OFF
OFF
1
Adaptation off
2
Adaptation on
3
Adaptation restart
42
Min. pre-heat time
0 ... set value of parameter 43
0,5
43
Max. pre-heat time
Set value of parameter 42 to 30 h
5
44
Min. jump back
temperature
0 ... 30°C
5
45
Without room sensor
0 ... 10°C
1
46
Pre-heat time at 0°C
0 ... 30 h
1
47
Lowering ramp
0 ... 500 %
100
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......