Operation
SDC / DHC
108
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Minimum
temperature
5 °C to setting value of parameter
02
20
02
Maximum
temperature
Setting value of parameter
01 to 95 °C
80
03
Boiler temperature
increase
–10 to 80 K
0
04
Buffer switching
differential
1 to 70 K
2
05
Forced discharge
OFF
OFF
1
In process water tank
2
In heating circuits
06
Follow-up switch-
on differential
OFF, (setting value of parameter
07 + 2 K) to 50 K
10
07
Follow-up switch-
off differential
1 K to (setting value of parameter
06 – 2 K)
5
08
Buffer start-up
protection
OFF
No start-up
protection
ON
Switching
differential
5 ... 20 K
5 K
09
Buffer discharge
protection
OFF
No discharge
protection
ON
ON
Discharge protection
active
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......